Heat Hero Direct & Direct Booster Kit
Heat Hero Direct has an open vent and a built-in gravity 44 kw cooling loop for safety. It can be linked into oil boilers, gas boilers, combi boilers, pressurised, open vented and single coil cylinders, underfloor heating, radiators and solar and also when there is no DWH cylinder. The heat circulates from the solid fuel boiler directly to the radiators, underfloor heating and DHW (without the use a heat exchanger) providing maximum efficiency.
HEAT HERO DIRECT INSTALLATION INSTRUCTIONS
- Heat Hero Direct should be installed a minimum of 1 metre and a maximum of 5 metres above the stove.
- The Circulating Pump. We recommend that an 8m Pump is installed and set to its fastest speed; to achieve maximum circulation and efficiency.
- The Pipe Thermostat must be of good quality and set at 55°. The pipe thermostat should be fitted as close to the solid fuel boiler as possible without damaging it.
- The Temperature Probe can be installed into one of the top tapping on the stove or on the gravity flow using a tee no more than 1 metre from the stove. It is important that the probe does not slow down the flow of water.
- The Thermal Safety Valve will open if the heat in the boiler exceeds 99°. This will allow water to pass through a 44kw cooling loop built into the Heat Hero Direct which will cool the gravity flow and bring the temperature of the boiler down.
- Expansion pipe of minimum ¾ “ diameter must be connected just above the Heat Hero Direct and before the circulating pump.
- The Heating Storage Tank should be a minimum of 1m above the highest point of the heating system. (e.g. above the Heat Hero Direct or above the radiators).
- The Cold Feed must be connected to the Gravity Return.
- Heating Zones If a heating system is zoned, at least one radiator zone must open automatically when the solid fuel thermostat turns on the circulating pump.